YXC8VZ3V-R TS IEC 60502-2 6/10 kV N2XSEYFGbY 6/10 kV, VDE 0276 | Structure
|
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: TS IEC 60502, VDE 0276 | The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, inward and is used in the ground. Also, these cables are used in places where mechanical stress. |
TECHNICAL SPECIFICATIONS | ||||||||
Normal Section | External Cable Diameter | Current-Carrying Capacity | Work Inductance | Work Capacity | Conductor DC Resistance (20°C) | Net Weight | Shipped in Length | |
mm2 | mm | In the air | Soil | mH/Km | µF/km | Ohm/Km | Kg/Km | Mt |
3×25/16 | 47.50 | 143 | 148 | 0.39 | 0.17 | 0.727 | 4040 | 500 |
3×35/16 | 50.50 | 173 | 178 | 0.37 | 0.19 | 0.524 | 4620 | 500 |
3×50/16 | 53.50 | 206 | 210 | 0.36 | 0.21 | 0.387 | 5320 | 500 |
3×70/16 | 57.50 | 257 | 256 | 0.34 | 0.24 | 0.268 | 6400 | 500 |
3×95/16 | 62.00 | 313 | 307 | 0.32 | 0.26 | 0.193 | 7620 | 500 |
3×120/16 | 65.50 | 360 | 349 | 0.31 | 0.29 | 0.153 | 8760 | 500 |
3×150/25 | 68.50 | 410 | 392 | 0.30 | 0.31 | 0.124 | 9970 | 500 |
3×185/25 | 72.50 | 469 | 443 | 0.29 | 0.34 | 0.0991 | 11560 | 250 |
3×240/25 | 81.50 | 553 | 513 | 0.28 | 0.39 | 0.0754 | 14500 | 250 |
3×300/25 | 84.50 | 635 | 579 | 0.27 | 0.42 | 0.0601 | 16660 | 250 |
3×400/35 | 91.50 | 731 | 650 | 0.26 | 0.48 | 0.0470 | 20260 | 250 |