H05Z1-K 300/500 V EN TS 50525-3-31 H07Z1-K 450/750 V EN TS 50525-3-31 | Structure
|
Technical Information Allowable operating temperature: 70°C Short circuit temperature: 160°C Series temperature min: -20°C | The Place Of Use In dry places, salt plants, distribution systems, cable is used as lighting and plumbing businesses. |
TECHNICAL SPECIFICATIONS | ||||||
Normal Section | External Cable Diameter | Current-Carrying Capacity | Conductor DC Resistance (20°C) | Net Weight | Shipped in Length | |
mm2 | mm | In the air | Soil | Ohm/Km | Kg/Km | Mt |
0.5 | 2.20 | 6 | – | 39.000 | 9.10 | 100 |
0.75 | 2.30 | 10 | – | 26.500 | 11.33 | 100 |
1 | 2.50 | 16 | – | 19.500 | 14.15 | 100 |
1.5 | 3.35 | 24 | 15 | 13.300 | 20.73 | 100 |
2.5 | 4.10 | 32 | 19 | 7.980 | 31.96 | 100 |
4 | 4.60 | 41 | 25 | 4.950 | 46.12 | 100 |
6 | 5.50 | 53 | 33 | 3.300 | 65.68 | 100 |
10 | 7.20 | 72 | 45 | 1.910 | 111.10 | 100 |
16 | 8.50 | 97 | 61 | 1.210 | 166.03 | 100 |
25 | 9.90 | 128 | 83 | 0.780 | 252.87 | 100 or 1000 |
35 | 11.40 | 156 | 103 | 0.554 | 344.70 | 100 or 1000 |
50 | 13.30 | 195 | 132 | 0.386 | 490.08 | 100 or 1000 |
70 | 14.90 | 243 | 165 | 0.272 | 671.93 | 100 or 1000 |
95 | 17.40 | 287 | 207 | 0.206 | 896.26 | 100 or 1000 |
120 | 19.00 | 342 | 235 | 0.161 | 1,122.49 | 100 or 1000 |
150 | 21.10 | 386 | – | 0.129 | 1,401.60 | 100 or 1000 |
185 | 24.10 | 441 | – | 0.106 | 1,721.39 | 100 or 1000 |
240 | 26.90 | 520 | – | 0.080 | 2,305.29 | 100 or 1000 |
300 | 30.60 | 605 | – | 0.064 | 2,805.38 | 100 or 1000 |
400 | 34.20 | 725 | – | 0.049 | 3,681.189 | 100 or 1000 |