YXC8VZ3V – R (6 – 10KV)

YXC8VZ3V-R TS IEC 60502-2 6/10 kV N2XSEYFGbY 6/10 kV, VDE 0276 Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. PVC fill
  8. Sheath separator
  9. Galvanized steel tape
  10. Flat galvanized steel wire
  11. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: TS IEC 60502, VDE 0276 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, inward and is used in the ground. Also, these cables are used in places where mechanical stress.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
3×25/16 47.50 143 148 0.39 0.17 0.727 4040 500
3×35/16 50.50 173 178 0.37 0.19 0.524 4620 500
3×50/16 53.50 206 210 0.36 0.21 0.387 5320 500
3×70/16 57.50 257 256 0.34 0.24 0.268 6400 500
3×95/16 62.00 313 307 0.32 0.26 0.193 7620 500
3×120/16 65.50 360 349 0.31 0.29 0.153 8760 500
3×150/25 68.50 410 392 0.30 0.31 0.124 9970 500
3×185/25 72.50 469 443 0.29 0.34 0.0991 11560 250
3×240/25 81.50 553 513 0.28 0.39 0.0754 14500 250
3×300/25 84.50 635 579 0.27 0.42 0.0601 16660 250
3×400/35 91.50 731 650 0.26 0.48 0.0470 20260 250