H05Z1 - U, H07Z1 - U R

H05Z1-U 300/500 V EN TS 50525-3-31 H07Z1-U/R 450/750 V EN TS 50525-3-31 Structure
  1. One or stranded copper conductor
  2. Isolated HFFR
Technical Information Allowable operating temperature: 70°C Short circuit temperature: 160°C Series temperature min: -20°C The Place Of Use In dry places, salt plants, distribution systems, cable is used as lighting and plumbing businesses.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil Ohm/Km Kg/Km Mt
0.5 2.00 7 36.000 8 100
0.75 2.20 12 24.500 11 100
1 2.30 18 18.100 13 100
1.5 2.75 24 15 12.100 19 100
2.5 3.35 32 19 7.410 31 100
4 3.80 42 25 4.610 44 100
6 4.30 54 33 3.080 63 100
10 5.50 73 45 1.830 105 100
16 6.45 98 61 1.150 161 100
1.5 2.96 24 15 12.100 20.73 100
2.5 3.60 32 19 7.410 32.03 100
4 4.15 42 25 4.610 47.98 100
6 4.75 54 33 3.080 68.16 100
10 5.80 73 45 1.830 108.95 100
16 6.80 98 61 1.150 165.55 100
25 8.30 129 83 0.727 256.74 100 or 1000
35 9.40 158 103 0.524 348.82 100 or 1000
50 11.00 197 132 0.387 477.91 100 or 1000
70 12.60 245 165 0.268 669.21 100 or 1000
95 14.80 290 207 0.193 924.25 100 or 1000
120 16.20 345 235 0.153 1,151.01 100 or 1000
150 18.00 390 0.124 1,423.45 100 or 1000
185 20.20 445 0.099 1,779.74 100 or 1000
240 22.90 525 0.075 2,321.21 100 or 1000
300 25.60 605 0.060 2,907.61 100 or 1000
400 28.80 725 0.047 3,734.49 100 or 1000