NHMH

NHMH 300/500V VDE 0250 TSEK Structure
  1. One or stranded copper conductor
  2. Isolated HFFR
  3. Fill HFFR
  4. HFFR outer sheath
Technical Information Allowable operating temperature: 70°C Short circuit temperature: 160°C Series temperature min: -20°C The Place Of Use Hospitals, shopping malls contains large numbers of people with it is used in facilities which have a fire hazard. These cables during a fire the flame conductors,heavy smoke do not form so that life and property safety is ensured.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil Ohm/Km Kg/Km Mt
2 x 1.5 7.90 18.5 26 12.100 99.00 100
2 x 2.5 8.70 25 34 7.410 129.76 100
2 x 4 10.00 34 44 4.610 181.75 100
2 x 6 11.40 43 56 3.080 250.38 100
2 x 10 14.40 60 75 1.830 404.54 100
2 x 16 16.40 80 98 1.150 568.81 100
3 x 1.5 8.30 18.5 26 12.100 115.34 100
3 x 2.5 9.20 25 34 7.410 155.51 100
3 x 4 10.80 34 44 4.610 225.81 100
3 x 6 12.30 43 56 3.080 313.51 100
3 x 10 15.30 60 75 1.830 498.50 100
3 x 16 17.40 80 98 1.150 709.64 100
4 x 1.5 8.30 18.5 26 12.100 122.26 100
4 X 2,5 9.20 25 34 7.410 168.15 100
4 x 4 11.00 34 44 4.610 251.71 100
4 x 6 12.50 43 56 3.080 352.24 100
4 x 10 15.30 60 75 1.830 552.49 100
4 x 16 17.40 80 98 1.150 799.63 100
5 x 1.5 9.60 18.5 26 12.100 163.24 100
5 x 2.5 10.70 25 34 7.410 224.80 100
5 x 4 12.80 34 44 4.610 335.76 100
5 x 6 14.60 43 56 3.080 469.84 100
5 x 10 18.10 60 75 1.830 747.10 100
5 x 16 21.20 80 98 1.150 1,105.66 100