NHXMH

NHXMH TSEK 300/500 V VDE 0250 Structure
  1. One or stranded copper conductor
  2. XLPE insulated
  3. Fill HFFR
  4. HFFR outer sheath
Technical Information Allowable operating temperature: 90°C Short circuit temperature: 250°C Series temperature min: -20°C The Place Of Use Hospitals, shopping malls contains large numbers of people with it is used in facilities which have a fire hazard. These cables are flame during a fire conductors,heavy smoke do not form so that life and property safety is ensured.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil Ohm/Km Kg/Km Mt
2 x 1.5 8.30 18.5 26 12.100 107.34 100
2 x 2.5 9.10 25 34 7.410 138.99 100
2 x 4 10.40 34 44 4.610 192.51 100
2 x 6 11.80 43 56 3.080 262.65 100
2 x 10 14.60 60 75 1.830 413.74 100
2 x 16 16.60 80 98 1.150 579.51 100
3 x 1.5 8.70 18.5 26 12.100 124.29 100
3 x 2.5 9.60 25 34 7.410 165.49 100
3 x 4 11.00 34 44 4.610 232.55 100
3 x 6 12.50 43 56 3.080 321.23 100
3 x 10 15.70 60 75 1.830 516.42 100
3 x 16 17.80 80 98 1.150 730.34 100
4 x 1.5 8.70 18.5 26 12.100 131.45 100
4 X 2,5 9.60 25 34 7.410 178.41 100
4 x 4 11.00 34 44 4.610 253.75 100
4 x 6 12.50 43 56 3.080 354.63 100
4 x 10 15.70 60 75 1.830 571.31 100
4 x 16 17.80 80 98 1.150 821.46 100
5 x 1.5 10.00 18.5 26 12.100 173.93 100
5 x 2.5 11.10 25 34 7.410 236.81 100
5 x 4 12.80 34 44 4.610 338.29 100
5 x 6 14.80 43 56 3.080 479.73 100
5 x 10 18.50 60 75 1.830 769.58 100
5 x 16 21.60 80 98 1.150 1,132.49 100