H05V-U / H07V-U/R

H05V-U 300/500 V VDE 0281 TS 9758 H07V-U/R 450/750 V VDE 0258 TS 9758 Structure
  1. One or stranded copper conductor
  2. PVC insulation
Technical Information Allowable operating temperature: 70°C Short circuit temperature: 160°C Test voltage(AC): 2kV – 2.5 kV Series temperature min: -5°C The Place Of Use This type of plaster or stucco into the pipe in humid places, they are used under the non conductors. Suitable for normal and mild operating conditions.
 TECHNICAL SPECIFICATIONS
Normal Section Medicine External Cable Diameter Current-Carrying Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2   mm In the air In The Pipe Ohm/Km Kg/Km Mt
0.5 H 05 V-U 2.00 11 36.000 8.00 100
0.75 H 05 V-U 2.15 14 24.500 11.00 100
1 H 05 V-U 2.30 18 18.100 13.00 100
1.5 H 07 V-U 2.75 24 15 12.100 20.00 100
2.5 H 07 V-U 3.35 32 19 7.410 31.00 100
4 H 07 V-U 3.80 42 25 4.610 45.00 100
6 H 07 V-U 4.30 54 33 3.080 64.00 100
10 H 07 V-U 5.50 73 45 1.830 107.00 100
16 H 07 V-U 6.50 98 61 1.150 162.75 100
1.5 H 07 V-R 2.96 24 15 12.100 21.00 100
2.5 H 07 V-R 3.60 32 19 7.410 33.00 100
4 H 07 V-R 4.15 42 25 4.610 49.00 100
6 H 07 V-R 4.75 54 33 3.080 70.00 100
10 H 07 V-R 5.80 73 45 1.830 111.00 100
16 H 07 V-R 6.80 98 61 1.150 168.00 100
25 H 07 V-R 8.30 129 83 0.727 260.00 100 or 1000
35 H 07 V-R 9.40 158 103 0.524 353.00 100 or 1000
50 H 07 V-R 11.00 197 132 0.387 483.00 100 or 1000
70 H 07 V-R 12.60 245 165 0.268 676.00 100 or 1000
95 H 07 V-R 14.80 290 207 0.193 934.00 100 or 1000
120 H 07 V-R 16.20 345 235 0.153 1,161.00 100 or 1000
150 H 07 V-R 18.00 390 0.124 1,436.00 100 or 1000
185 H 07 V-R 20.20 445 0.099 1,796.00 100 or 1000
240 H 07 V-R 22.90 525 0.075 2,342.00 100 or 1000
300 H 07 V-R 25.60 605 0.060 2,933.00 100 or 1000
400 H 07 V-R 28.80 725 0.047 3,765.00 100 or 1000