N2XS(F)2Y 20.3/ 35 kV TSEK | Structure
|
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool temperature min: -20°C Standard: VDE 0276 TS IEC 60502-2 | The Place Of Use These cables where the short circuit currents are large residential fed with electrical energy and industrial zones the load increases, the expected networks, outward, cable channels, inward and is used in the ground. The cable from mechanical impacts tape water bottle holder in the case of the water by doing the task blocks. |
TECHNICAL SPECIFICATIONS | ||||||||
Normal Section | External Cable Diameter | Current-Carrying Capacity | Work Inductance | Work Capacity | Conductor DC Resistance (20°C) | Net Weight | Shipped in Length | |
mm2 | mm | In the air | Soil | mH/Km | µF/km | Ohm/Km | Kg/Km | Mt |
1×35/16 | 35.00 | 169 | 165 | 0,69 | 0,12 | 0,524 | 1260 | 1000 |
1×50/16 | 36.50 | 249 | 232 | 0,66 | 0,13 | 0,387 | 1420 | 1000 |
1×70/16 | 38.00 | 30 | 284 | 0,63 | 0,14 | 0,268 | 1665 | 1000 |
1×95/16 | 40.00 | 375 | 339 | 0,60 | 0,15 | 0,193 | 1955 | 1000 |
1×120/16 | 41.00 | 430 | 385 | 0,59 | 0,17 | 0,153 | 2230 | 1000 |
1×150/25 | 43.00 | 485 | 430 | 0,57 | 0,18 | 0,124 | 2610 | 1000 |
1×185/25 | 44.50 | 554 | 484 | 0,55 | 0,19 | 0,0991 | 3000 | 1000 |
1×240/25 | 46.50 | 653 | 559 | 0,53 | 0,21 | 0,0754 | 3575 | 1000 |
1×300/25 | 49.00 | 739 | 627 | 0,51 | 0,23 | 0,0601 | 4200 | 1000 |
1×400/35 | 52.00 | 842 | 701 | 0,49 | 0,25 | 0,0470 | 5200 | 500 |
1×500/35 | 55.00 | 965 | 786 | 0,48 | 0,27 | 0,0366 | 6245 | 500 |
1×600/35 | 60.00 | 1096 | 875 | 0,46 | 0,30 | 0,0283 | 7630 | 500 |