N2XS(FL)2Y 20.3/35 kV TSEK | Structure
|
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool temperature min: -20°C Standard: VDE 0276 TS IEC 60502-2 | The Place Of Use These cables where the short circuit currents are large residential load fed with electrical energy and industrial zones expected increases in the networks, outward, cable channels, inward, and the ground is used. Take water from mechanical impacts of the cable the bottle holder prevents the water by doing the task in the case of the tape. |
TECHNICAL SPECIFICATIONS | ||||||||
Normal Section | External Cable Diameter | Current-Carrying Capacity | Work Inductance | Work Capacity | Conductor DC Resistance(20°C) | Net Weight | Shipped in Length | |
mm2 | mm | In the air | Soil | mH/Km | µF/km | Ohm/Km | Kg/Km | Mt |
1×35/16 | 36.00 | 169 | 165 | 0,69 | 0,12 | 0,524 | 1230 | 1000 |
1×50/16 | 37.20 | 249 | 232 | 0,66 | 0,13 | 0,387 | 1430 | 1000 |
1×70/16 | 39.20 | 308 | 284 | 0,63 | 0,14 | 0,268 | 1680 | 1000 |
1×95/16 | 40.80 | 375 | 339 | 0,30 | 0,15 | 0,193 | 1980 | 1000 |
1×120/16 | 42.60 | 430 | 385 | 0,59 | 0,17 | 0,153 | 2300 | 1000 |
1×150/25 | 43.80 | 485 | 430 | 0,57 | 0,18 | 0,124 | 2740 | 1000 |
1×185/25 | 45.80 | 554 | 484 | 0,55 | 0,19 | 0,0991 | 3100 | 1000 |
1×240/25 | 48.20 | 653 | 559 | 0,53 | 0,21 | 0,0754 | 3640 | 1000 |
1×300/25 | 50.20 | 739 | 627 | 0,51 | 0,23 | 0,0601 | 4450 | 1000 |
1×400/35 | 54.20 | 842 | 701 | 0,49 | 0,25 | 0,0470 | 5400 | 500 |
1×500/35 | 57.20 | 965 | 786 | 0,48 | 0,27 | 0,0366 | 6500 | 500 |
1×630/35 | 62.20 | 1096 | 875 | 0,46 | 0,30 | 0,0283 | 7850 | 500 |