N2XSYR(AL) Y( 20,3 – 35KV)

N2XSYR(AL)Y 20.3/35 kV TSEK Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. Polyester tape
  8. Sheath separator
  9. Alüminyum tel zırh
  10. Polyester tape
  11. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: VDE 0276 TS IEC 60502-2 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, and inward in the ground is used. Also, these cables are used in places where mechanical stress.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
1×35/16 40.00 177 165 0,73 0,12 0,524 2000 1000
1×50/16 41.00 253 232 0,71 0,13 0,387 2210 1000
1×70/16 43.00 312 282 0,68 0,14 0,268 2490 1000
1×95/16 46.00 373 332 0,64 0,15 0,193 3000 1000
1×120/16 47.50 425 373 0,62 0,17 0,153 3340 1000
1×150/25 49.00 476 410 0,60 0,18 0,214 3750 1000
1×185/25 51.50 536 456 0,58 0,19 0,0991 4250 1000
1×240/25 53.50 618 517 0,56 0,21 0,0754 4900 500
1×300/25 56.50 687 569 0,54 0,23 0,0601 5650 500
1×400/35 60.00 770 621 0,51 0,25 0,0470 6790 500
1×500/35 63.50 859 678 0,50 0,27 0,0366 7980 500
1×630/35 68.50 947 732 0,49 0,30 0,0283 9610 500