NA2XS(FL)2Y 20.3/35 kV TSEK | Structure
|
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool temperature min: -20°C Standard: VDE 0276 TS IEC 60502-2 | The Place Of Use These cables where the short circuit currents are large residential fed with electrical energy and industrial zones the load increases, the expected networks, outward, cable channels, inward and under the Earth is used. Water of the cable from mechanical impacts the bottle holder prevents the water by doing the task in case you receive the tape. |
TECHNICAL SPECIFICATIONS | ||||||||
Normal Section | External Cable Diameter | Current-Carrying Capacity | Work Inductance | Work Capacity | Conductor DC Resistance (20°C) | Net Weight | Shipped in Length | |
mm2 | mm | In the air | Soil | mH/Km | µF/km | Ohm/Km | Kg/Km | Mt |
1×35/16 | 36.00 | 157 | 134 | 0.69 | 0.11 | 0.868 | 1115 | 1000 |
1×50/16 | 37.00 | 189 | 195 | 0.66 | 0.12 | 0.641 | 1185 | 1000 |
1×70/16 | 38.50 | 270 | 237 | 0.63 | 0.13 | 0.443 | 1320 | 1000 |
1×95/16 | 40.00 | 328 | 282 | 0.61 | 0.14 | 0.320 | 1460 | 1000 |
1×120/16 | 41.50 | 378 | 320 | 0.59 | 0.15 | 0.253 | 1585 | 1000 |
1×150/25 | 43.00 | 425 | 353 | 0.58 | 0.16 | 0.206 | 1815 | 1000 |
1×185/25 | 45.00 | 485 | 396 | 0.57 | 0.18 | 0.1640 | 1990 | 1000 |
1×240/25 | 47.00 | 573 | 457 | 0.55 | 0.19 | 0.1250 | 2235 | 1000 |
1×300/25 | 49.00 | 652 | 511 | 0.54 | 0.21 | 0.1000 | 2440 | 1000 |
1×400/35 | 52.00 | 740 | 566 | 0.53 | 0.23 | 0.0778 | 2845 | 1000 |
1×500/35 | 55.00 | 838 | 630 | 0.51 | 0.25 | 0.0605 | 3290 | 1000 |
1×630/35 | 59.00 | 953 | 719 | 0.50 | 0.29 | 0.0469 | 3820 | 500 |