YXC7V - R (18 – 30KV)

YXC7V-R TS IEC 60502-2 18/30 kV 18/30 kV N2XSY VDE 0276 Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. Polyester Tape
  8. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: VDE 0276 TS IEC 60502-2 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, and inward in the ground is used. Also, these cables are used in places where mechanical is enforced.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance(20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
1×35/16 30.00 169 165 0,694 0,12 0,524 1160 1000
1×50/16 32.00 248 232 0,668 0,14 0,387 1330 1000
1×70/16 33.50 307 284 0,637 0,15 0,268 1570 1000
1×95/16 35.50 373 339 0,612 0,17 0,193 1870 1000
1×120/16 37.00 439 385 0,593 0,18 0,153 2160 1000
1×150/25 38.50 484 430 0,578 0,19 0,124 2550 1000
1×185/25 40.50 552 484 0,561 0,21 0,0991 2950 1000
1×240/25 42.50 649 559 0,541 0,23 0,0754 3520 1000
1×300/25 45.50 737 627 0,524 0,25 0,0601 4170 1000
1×400/35 48.50 841 701 0,503 0,28 0,0470 5180 1000
1×500/35 51.20 963 786 0,487 0,30 0,0366 6250 500
1×630/35 56.50 1094 875 0,47 0,33 0,0283 7700 500