YXC7V - R (3.6 – 6kv)

YXC7V-R 3.6/6 kV TS IEC 60502-2 N2XSY 3.6/6 kV, VDE 0276 Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. Polyester Tape
  8. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: TS IEC 60502 - VDE 0276 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, and inward in the ground is used. Also, these cables are used in places where mechanical is enforced.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
1×25/16 18.00 162 166 0.68 0.25 0.727 620 1000
1×35/16 19.50 196 198 0.66 0.28 0.524 710 1000
1×50/16 20.50 235 234 0.63 0.32 0.387 850 1000
1×70/16 22.00 293 286 0.60 0.37 0.268 1060 1000
1×95/16 24.00 358 341 0.58 0.41 0.193 1320 1000
1×120/16 25.00 413 387 0.56 0.46 0.153 1570 1000
1×150/25 26.50 469 431 0.54 0.50 0.124 1930 1000
1×185/25 28.50 537 485 0.53 0.54 0.0991 2290 1000
1×240/25 31.00 633 559 0.51 0.59 0.0754 2850 1000
1×300/25 34.00 722 626 0.49 0.60 0.0601 3470 1000
1×400/35 37.50 826 696 0.47 0.64 0.0470 4440 1000
1×500/35 41.50 943 777 0.46 0.67 0.0366 5490 1000
1×630/35 46.00 1069 860 0.44 0.74 0.0283 6860 1000