YXC8V - R (20.3 – 35KV)

YXC8V-R 20.3/35 kV TSEK N2XSEY 20.3/35 kV Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. Fill
  8. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: VDE 0276 TS IEC 60502-2 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, inward and is used in the ground. Also, these cables are used in places where mechanical is enforced.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance(20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
3×35/16 72.50 182 183 0,48 0,10 0,524 6380 500
3×50/16 75.00 217 214 0,45 0,11 0,387 7080 250
3×70/16 78.50 269 261 0,42 0,12 0,268 8170 250
3×95/16 82.50 326 313 0,41 0,14 0,193 9380 250
3×120/16 86.50 377 356 0,39 0,15 0,153 10630 250
3×150/25 89.00 426 400 0,37 0,16 0,124 11880 250
3×185/25 93.50 488 441 0,36 0,17 0,0991 13660 200
3×240/25 98.50 576 510 0,34 0,18 0,0754 15980 200
3×300/25 104.50 654 604 0,33 0,20 0,0601 18590 200
3×400/35 111.00 754 688 0,31 0,24 0,0470 22240 200