YXC8VZ3V - R (12 – 20 KV)

YXC8VZ3V-R TS IEC 60502-2 12/20 kV N2XSEYFGbY 12/20 kV VDE 0276 Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. PVC fill
  8. Sheath separator
  9. Galvanized steel tape
  10. Flat galvanized steel wire
  11. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: VDE 0276 TS IEC 60502-2 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, and inward in the ground is used. Also, these cables are used in places where mechanical stress.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
3×35/16 60.50 182 183 0,42 0,14 0,524 6060 500
3×50/16 63.50 218 214 0,40 0,16 0,387 6790 500
3×70/16 68.00 271 264 0,38 0,17 0,268 7940 500
3×95/16 72.00 323 313 0,36 0,19 0,193 9230 250
3×120/16 76.00 374 356 0,34 0,21 0,153 10530 250
3×150/25 79.00 419 400 0,33 0,23 0,124 11980 250
3×185/25 84.00 488 452 0,32 0,24 0,0991 13720 250
3×240/25 91.00 579 530 0,31 0,28 0,0754 16460 250
3×300/25 94.50 654 604 0,30 0,30 0,0601 18740 250
3×400/35 102.00 754 688 0,28 0,33 0,0470 22660 250