YXC8VZ3V – R (18 – 30KV)

YXC8VZ3V-R TS IEC 60502-2 18/30 kV N2XSEYFGbY 18/30 kV VDE 0276 Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. PVC fill
  8. Sheath separator
  9. Galvanized steel tape
  10. Flat galvanized steel wire
  11. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: VDE 0276 TS IEC 60502-2 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, and inward in the ground is used. Also, these cables are used in places where mechanical stress.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
3×35/16 73.00 182 183 0,46 0,11 0,524 8000 500
3×50/16 76.00 217 214 0,44 0,12 0,387 8900 250
3×70/16 80.50 269 261 0,41 0,14 0,268 10330 250
3×95/16 84.50 326 313 0,39 0,16 0,193 11740 250
3×120/16 88.50 377 356 0,38 0,17 0,153 13050 250
3×150/25 91.00 426 400 0,36 0,19 0,124 14420 250
3×185/25 96.00 488 441 0,35 0,20 0,0991 16220 200
3×240/25 101.00 576 510 0,33 0,21 0,0754 18800 200
3×300/25 107.00 654 604 0,32 0,23 0,0601 21640 200
3×400/35 114.50 754 688 0,30 0,25 0,0470 25620 200