YXC8VZ3V - R ( 3.6 – 6kv)

YXC8VZ3V-R 3.6/6 kV TS IEC 60502-2 N2XSEYFGbY 3.6/6 kV, VDE 0276 Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. PVC fill
  8. Sheath separator
  9. Galvanized steel tape
  10. Flat galvanized steel wire
  11. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: VDE 0276 TS IEC 60502-2 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, and inward in the ground is used. Also, these cables are used in places where mechanical stress.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
3×25/16 42.50 141 149 0.37 0.20 0.727 3470 1000
3×35/16 46.00 171 176 0.35 0.22 0.524 4110 1000
3×50/16 49.50 196 208 0.34 0.25 0.387 4760 1000
3×70/16 53.00 249 255 0.32 0.28 0.268 5780 500
3×95/16 57.00 307 307 0.30 0.32 0.193 6910 500
3×120/16 61.00 353 353 0.29 0.35 0.153 8090 500
3×150/25 63.50 406 396 0.28 0.38 0.124 9270 500
3×185/25 68.50 464 447 0.27 0.42 0.0991 10860 500
3×240/25 77.00 548 523 0.26 0.47 0.0754 13610 250
3×300/25 82.00 632 581 0.26 0.48 0.0601 16130 250
3×400/35 90.00 726 653 0.25 0.52 0.0470 19920 250