YXC8VZ4V – R (20.3 – 35KV)

YXC8VZ4V-R 20.3/35 kV TSEK N2XSEYBY 20.3/35 kV Structure
  1. Multi-stranded copper conductor
  2. IC a semiconductor
  3. XLPE insulated
  4. External semiconductor
  5. Semiconductor band
  6. Copper screen
  7. Fill
  8. Dec sheath
  9. Double galvanized steel tape
  10. PVC outer sheath
Technical Information Maximum operating temperature: 90°C Maximum short circuit temperature: 250°C (+≤ 5 sec) Cool min Temperature: -5°C Standard: TS IEC 60502-2 VDE0276 The Place Of Use These cables where the short circuit currents are large residential and fed with electrical energy in industrial zones, outward, cable channels, inward and is used in the ground. Also, these cables are used in places where mechanical stress.
TECHNICAL SPECIFICATIONS
Normal Section External Cable Diameter Current-Carrying Capacity Work Inductance Work Capacity Conductor DC Resistance (20°C) Net Weight Shipped in Length
mm2 mm In the air Soil mH/Km µF/km Ohm/Km Kg/Km Mt
3×50/16 82.50 214 214 0,44 0,11 0,387 10960 250
3×70/16 86.50 269 261 0,42 0,12 0,268 12280 250
3×95/16 90.50 326 313 0,41 0,14 0,193 13800 250
3×120/16 94.50 377 356 0,39 0,15 0,153 15170 200
3×150/25 97.00 426 400 0,37 0,16 0,124 16600 200
3×185/25 102.00 510 441 0,36 0,17 0,0991 18680 200
3×240/25 107.00 579 510 0,34 0,18 0,0754 21250 200
3×300/25 113.00 654 604 0,32 0,23 0,0601 24220 200
3×400/35 120.00 754 688 0,30 0,25 0,0470 28350 200